The Model SNR701 is an industrial flammability analyzer that measures total flammable vapor concentrations from 0 to 100% of the Lower Flammable Limit (LFL) using a heated flame cell. The pneumatic assembly is maintained at 60°C (140°F) to prevent condensation. It mounts directly to process ductwork with dimensions of 16" H × 12.1" W × 8.5" D. Power requirement is 120 VAC ±10%-15% at 50/60 Hz, with 400 W maximum draw; 230 VAC is optional. The flame cell is rated Explosion Proof Class I, Division 1 and the enclosure is TYPE 12/13. Standard outputs include two 4-20 mA analog signals, RS-485 serial with Modbus protocol, and six relays. Accuracy is ±3% of full scale or ±10% of applied gas, whichever is greater. Zero stability is ±1% in 30 days. The unit is FM certified with optional FMc.
The Model SNR701 is an industrial strength assembly consisting of a heated flame cell and an integrated controller that continuously measures total flammable vapor concentrations from 0 to 100% of the Lower Flammable Limit (LFL) range. Optional modifications allow the SNR701 to sample low oxygen and inert atmospheres.
| Control Instruments Corp. | |
|---|---|
| Product Category | Gas Instruments |
| Product Number | PrevEx Model SNR701 |
| Product Name | Vapor Flammability Analyzer |
| Measurement Type | %LEL or %LFL |
| Application | Ambient Air Monitoring; Process Gas |
| Gas Types | Combustible; Hydrocarbons; (0-100% LFL); H2; (0-100% LFL); Methane (CH4) / Natural Gas; (0-100% LFL) |
| Electrical Outputs | Current; Switch or Relay |
| Display | Digital |