CSA Group Switchboards (Tri-National standard, with UL 891 and ANCE NMX-J-118/2) C22.2 NO. 244-05 (R2015)

Description
Preface This is the common ANCE, CSA, and UL standard for Switchboards. It is the Second edition of NMX-J-118/2-ANCE, the First edition of C22.2 No. 244, and the Eleventh edition of UL 891. Scope 1.1.1 This Standard applies to switchboards nominally rated at 600 V or less and intended for use in accordance with the Canadian Electrical Code, Part 1 (CE Code, Part 1), the National Electrical Code (NEC), ANSI/NFPA 70, and the Mexican Standard for Electrical Installations (Utility), NOM-001-SEDE. 1.1.2 In this standard the term switchboard is intended to refer to a dead-front switchboard. 1.1.3 These requirements do not cover the following switchboard types: preset and dimmer control (theater), live front, railway control or electrification; or constructions intended only for receiving motor control center units. 1.1.4 These requirements cover switchboards for use on circuits having available rms symmetrical short-circuit currents of not more than 200 000 A.
Description
Preface This is the common ANCE, CSA, and UL standard for Switchboards. It is the Second edition of NMX-J-118/2-ANCE, the First edition of C22.2 No. 244, and the Eleventh edition of UL 891. Scope 1.1.1 This Standard applies to switchboards nominally rated at 600 V or less and intended for use in accordance with the Canadian Electrical Code, Part 1 (CE Code, Part 1), the National Electrical Code (NEC), ANSI/NFPA 70, and the Mexican Standard for Electrical Installations (Utility), NOM-001-SEDE. 1.1.2 In this standard the term switchboard is intended to refer to a dead-front switchboard. 1.1.3 These requirements do not cover the following switchboard types: preset and dimmer control (theater), live front, railway control or electrification; or constructions intended only for receiving motor control center units. 1.1.4 These requirements cover switchboards for use on circuits having available rms symmetrical short-circuit currents of not more than 200 000 A.

Suppliers

Company
Product
Description
Supplier Links
Switchboards (Tri-National standard, with UL 891 and ANCE NMX-J-118/2) - C22.2 NO. 244-05 (R2015) - CSA Group
Toronto, Ontario, Canada
Switchboards (Tri-National standard, with UL 891 and ANCE NMX-J-118/2)
C22.2 NO. 244-05 (R2015)
Switchboards (Tri-National standard, with UL 891 and ANCE NMX-J-118/2) C22.2 NO. 244-05 (R2015)
Preface This is the common ANCE, CSA, and UL standard for Switchboards. It is the Second edition of NMX-J-118/2-ANCE, the First edition of C22.2 No. 244, and the Eleventh edition of UL 891. Scope 1.1.1 This Standard applies to switchboards nominally rated at 600 V or less and intended for use in accordance with the Canadian Electrical Code, Part 1 (CE Code, Part 1), the National Electrical Code (NEC), ANSI/NFPA 70, and the Mexican Standard for Electrical Installations (Utility), NOM-001-SEDE. 1.1.2 In this standard the term switchboard is intended to refer to a dead-front switchboard. 1.1.3 These requirements do not cover the following switchboard types: preset and dimmer control (theater), live front, railway control or electrification; or constructions intended only for receiving motor control center units. 1.1.4 These requirements cover switchboards for use on circuits having available rms symmetrical short-circuit currents of not more than 200 000 A.

Preface
This is the common ANCE, CSA, and UL standard for Switchboards. It is the Second edition of NMX-J-118/2-ANCE, the First edition of C22.2 No. 244, and the Eleventh edition of UL 891.
Scope
1.1.1
This Standard applies to switchboards nominally rated at 600 V or less and intended for use in accordance with the Canadian Electrical Code, Part 1 (CE Code, Part 1), the National Electrical Code (NEC), ANSI/NFPA 70, and the Mexican Standard for Electrical Installations (Utility), NOM-001-SEDE.
1.1.2
In this standard the term switchboard is intended to refer to a dead-front switchboard.
1.1.3
These requirements do not cover the following switchboard types: preset and dimmer control (theater), live front, railway control or electrification; or constructions intended only for receiving motor control center units.
1.1.4
These requirements cover switchboards for use on circuits having available rms symmetrical short-circuit currents of not more than 200 000 A.

Supplier's Site

Technical Specifications

  CSA Group
Product Category Standards and Technical Documents
Product Number C22.2 NO. 244-05 (R2015)
Product Name Switchboards (Tri-National standard, with UL 891 and ANCE NMX-J-118/2)
Unlock Full Specs
to access all available technical data

Similar Products